Reserved 11 4 commissioning operations maintenance inspection and testing.
Class a ovens and furnaces.
This additional equipment is sized based on the volume of solvent being evaporated and the maximum operating temperature.
Reserved 11 2 location and construction.
The single most important thing to know safety first.
An oven with an interior volume of 100 ft3 and exhaust ventilation of 125 ft3 min would require 3 2 min purge time 100 ft3 x 4 400 125 3 2 min.
Nfpa 86 defines ovens for these applications as class a ovens.
Ovens are separated by class per nfpa 86.
Order additional factory installed options for our heratherm and vacutherm lines.
Reserved 11 3 heating systems.
In order to keep flammable vapor concentration at safe levels class a ovens include additional equipment to provide safety ventilation.
Whether you have a direct gas fired furnace or an electrically heated industrial oven understanding and following the nfpa 86 standard for ovens and furnaces can minimize the risk of a catastrophic event at your plant.
Known for tighter temperature tolerances higher yields and consistent repeatable results.
And any other heated enclosure used for processing of materials and related equipment.
This standard shall apply to class a class b class c and class d ovens dryers and furnaces.
Class a ovens must have a purge period before the heat source can be energized.
Efficient safe easy to use.
Nfpa 86 2019 pertains to class a class b class c and class d ovens dryers and furnaces as well as thermal oxidizers.
An oven or furnace that has heat utilization equipment operating at approximately atmospheric pressure wherein there is a potential explosion or fire hazard that could be occasioned by the presence of flammable volatiles or combustible materials processed or heated in the furnace.
Browse our accessories to optimize the performance of your ovens and furnaces including oven floor stands and stacking kits furnace exhaust connections and racks and shelves.
The tfd class a walk in oven is specifically designed to meet nfpa 86 requirements.
11 7 low oxygen atmosphere class a ovens with solvent recovery.
Industrial ovens and industrial furnaces in batch and conveyor configurations for thermal processing applications such as annealing curing drying heat treating sterilizing burn in and testing.
The large size and maximum 343 650 temperature of the tfd walk in ovens make these models a perfect choice for curing and drying large size or large batch components.
11 6 safety ventilation for class a ovens.
This purge period must be long enough to get at least four air changes of interior volume.
A 1 1 explosions and fires in fuel fired and electric heat utilization equipment constitute a loss potential in life property and production.